Smart-UPS 750/1000/1500/2200/3000 VA  100/120/230 Vac / 500 VA 100 Vac  Tower
8
Configuration
UPS Settings
Start up Settings
Configure these settings at initial start up, using the display interface. As an alternative, configuration can be 
performed using PowerChute
™ 
software.
Note:
 During start up, use the display interface to configure these settings. If nothing is selected, the 
unit will use the default settings.
General Settings
Configure these settings at any time. Use the display interface or PowerChute
 
software.
Function
Factory Default
Options
Description
Language
English
• English
• French*
• German*
• Spanish*
• Italian*
• Portuguese*
• Japanese*
The language for the display interface.
*Language options will vary by model.
Local Power 
Quality
Good
• Good
• Fair
• Poor
Select the quality of input utility power.
• If Good is selected, the unit will go on battery power 
more often to provide the cleanest power supply to the 
connected equipment.
• If Poor is selected, the UPS will tolerate more 
fluctuations in power and will go on battery power less 
often. 
If unsure of the local power quality, select Good.
Menu Type
Standard
Standard or 
Advanced
The Standard menus display a limited set of menus 
and options. The advanced menus include all 
parameters.
Function
Factory Default
Options
Description
High Transfer Point 
100 Vac:
108 Vac
108 Vac - 114 Vac
To avoid unnecessary battery usage, set the transfer 
point higher if the utility voltage is chronically high and 
the connected equipment is known to work under this 
condition. The Power Quality setting will 
automatically change this setting. 
Note: Use the Advanced Menus to configure this 
setting.
120 Vac:
127 Vac
127 Vac - 136 Vac
230 Vac:
253 Vac
253 Vac - 265 Vac