GE LTC MAP User Manual

Page of 68
 
3-24
 
Section 3:  Installation 
February 3, 2000 
70055MP Revision D 
 
Once power is applied, and configuration parameters have been uploaded 
to the monitor, the monitor enters normal operation and begins monitoring 
sensor and voltage inputs. 
Refer to Section 4 - Operation for further operation procedures. 
 
Calibrate Tap Position 
1.  Press the 
Setup
 button to display the Tap Position Input Calibration 
Low Point screen.  
  T  A  P    P  O  S  I  T  I  O  N    I  N  P  U  T   
        C  A  L  I  B  R  A  T  I  O  N           
          L  O  W    P  O  I  N  T  :           
 
â
              5                   
á
   
 
  The Setup button is located on the upper left corner of back side the 
CPU board. 
2.  Observe and record the actual tap position of the LTC at the TAP 
Position Indicator. 
3.  Adjust the value of the low tap position calibration point to the value 
observed in Step 2 by pressing â or á  until the correct value is 
displayed 
4.  Press 
Setup
 to display the Tap Position High Point Calibration screen.  
 
  T  A  P    P  O  S  I  T  I  O  N    I  N  P  U  T   
        C  A  L  I  B  R  A  T  I  O  N           
        H  I  G  H    P  O  I  N  T  :           
 
â
              6                   
á
   
5.  Manually move the tap up one position. 
6.  Adjust the value of the high tap position calibration point up one 
position from the low calibration point by pressing â or á until the 
correct value is displayed. 
7.  Press 
Setup
 to exit the Calibration and return to normal operation.