GE LTC MAP User Manual

Page of 68
5-2 
Section 5:  Troubleshooting Procedures 
February 3, 2000 
70055MP Revision D 
Table 5-1: Common Troubleshooting Procedures (Cont’d) 
Condition 
Possible Cause(s) 
Corrective Action 
Incorrect Tap Position 
Displayed/Recorded. 
Sensor Input and Sensor Common  
connections reversed. 
Battery supply for OEM resistor string 
not stable or floating to ground 
causing a ground loop. 
Disconnect inputs and test voltage on the wires 
with a volt meter referenced to earth ground. 
Disconnect inputs and test voltage on the wires 
with a volt meter referenced to earth ground. 
Cut or remove the strap for Sensor Common input 
to chassis ground connection on the circuit 
board. 
Use a DC voltage from the monitor, rather than a 
battery, to supply the OEM resistor string. 
Heater ON at ambient over  
60 ºF (15.5 ºC). 
Faulty heater. 
 
Disconnect heater from I/O board; contact Reuter-
Stokes, Inc.. 
Heater not ON at ambient under 50 ºF 
(10 ºC). 
Faulty connections. 
Check heater connections.