GE 68K System User Manual

Page of 112
68K System Monitor
User's Guide
GE Energy Services
General
SWM0023-1.00 -2
Full Release
3-69
SC - Select Active Configuration
Platform
o
CPM
o
D20
D20 Base
o
D20 ME
D20 Base
þ
D20/200
CCU Base
þ
D20/200 ME
CCU Base
þ
D25
Description
Use this command to select one of the stored configurations as the active
configuration.
The system is halted and the stored configuration is uncompressed (if necessary) and
written into NVRAM (local on the D25, global on a D200) as the new configuration.
The selected configuration file is marked as the active configuration.
Note:
Upon completion, the Monitor leaves the system halted so that you can
restart the system with the new configuration.
Syntax
Below is usage and syntax information for this command
Command Format
sc (file_num | file_name) [BaseAddress]
Variables
None
Parameters
file_num
=  The query configuration storage parameters
    command displays all existing files, giving
    each a numerical index. The monitor uses this
    index with the command to specify the file
    that it will copy into memory and make
    active.
file_name
=  The name of the configuration file to select.
    The command will select the first matching
     configuration it finds.
BaseAddress  =  base address at which to write the new
     configuration
Example
Type sc config.bin and press 
ENTER
.
Results: The monitor selects the stored configuration
"config.bin" as the active configuration and copies it
into NVRAM, overwriting the existing configuration.
Special
Considerations
Once this function is invoked, it may take some time for the
configuration to be decompressed (if necessary), and written
into memory.