Omega OMB-DAQBOARD-3000 User Manual

Page of 108
More Examples of Control Outputs 
Detection on an Analog Input, DAC and P2C Updates 
Update Mode:  Update on True and False  
Criteria: Ch 5 example: Below Limit;   Ch 4 example: Inside Window 
 
 
In this example Channel 5 has been programmed with reference to one setpoint [Limit A], defining a low 
limit; and Channel 4 has been programmed with reference to two setpoints [Limits A and B] which define 
a window for that channel. 
 
Channel 
Condition 
State of 
Detect Signal 
Action 
True 
When Channel 5 analog input voltage is below the limit A, 
update DAC1 with Output Value 0.0V. 
Below Limit A 
(for Channel 5) 
False 
When the above stated condition is false, update DAC1 with 
the Output Value of minus 1.0V. 
True 
When Channel 4 analog input voltage is within the window, 
update P2C with 70h. 
4 Within 
Window 
(Between Limit A 
and Limit B) for 
Channel 4 
False 
When the above stated condition is false (Channel 4 analog 
input voltage is outside the window) update P2C with 30h. 
 
 
Limit A 
(for Channel 5) 
 
 
DAC1 
 
Detection 
(for Channel 5) 
 
 
Limit A 
(for Channel 4) 
Limit B 
(for Channel 4) 
 
 
P2C 
 
Detection 
Signal 
(for Channel 4) 
 
Analog Inputs with Setpoints 
Update on True and False 
DaqBoard/3000 Series User’s Manual
 908794
 
Setpoint Configuration for Output Control      6-7