Yamaha ERCX User Manual

Page of 52
33
CHAPTER2  Ethernet Unit
Checkpoints
• Check the settings after referring to “2-
4-2 Setting the IP address” p. 10, “2-4-
3 Setting the subnet mask” p. 12, and 
“2-4-4 Setting the gateway” p. 13.
• Try substituting the Ethernet unit.
• Check that the IP address of the  
controller you are attempting to 
connect with is correct.
• Check that the port No. of the  
controller you are attempting to 
connect with is correct.
• When connected, the message “telnet is 
already used!” appears.
• Alarm message appears when 
connected.
• Connect the TPB and check for an 
alarm.
• Status led is lit up in red.
• Check if the IP address and MAC 
address have a correct match by using 
the “arp” command incorporated in the 
OS.
• Check all devices on the network to 
find if the same IP address is being 
used.
• Check if the traffic load is appropriate.
• See “2-4-1 Enabling the Ethernet Unit” 
(p. 9) and check if the Ethernet Unit is 
enabled.
• Check the I/O signal (Check on the 
sequencer monitor, etc.)
• Communication error is issued when 
TPB is connected to controller.
• Reply comes back after axis movement 
or writing data.
Action
• Redo the IP address, subnet mask and 
gateway settings correctly. Then turn 
on the controller power again.
• If operation returns to normal, then the 
Ethernet unit is probably defective, so 
replace the Ethernet unit.
• Enter the correct IP address.
• Enter the correct IP address.
• Await termination of current TELNET 
connection.
• Troubleshoot according to the type of 
alarm.
• If the IP address and MAC address do 
not match each other, then the IP 
address is wrong, so try redoing the 
settings.
• If found to be the same as another 
device, change the setting.
• Change the network structure to get a 
smaller traffic load.
• Enable the Ethernet unit and turn on 
the power to the controller again.
• Always use a pulse input for the 
custom command input.
• When issuing TELNET commands, do 
not run commands from the I/O or RS-
232C.
No.
2
3
Probable causes
Wrong IP 
address, subnet 
mask or gateway 
settings on 
controller.
Ethernet unit is 
defective
Wrong IP 
address used 
during Telnet 
connection
Wrong Port No. 
used during 
TELNET 
connection.
The controller is 
already logged in 
with another 
TELNET 
terminal.
Alarm issued to 
controller.
IP address is the 
same as another 
network device.
Network traffic 
(communication 
data load) is too 
heavy.
Ethernet unit is 
not enabled and 
not identified 
(recognized) by 
controller.
I/O custom 
command input 
signal is set ON.
Commands such 
as origin return, 
axis movement 
commands, or 
data write 
commands are 
being run from 
I/O or RS/232C.
7)
8)
1)
2)
3)
4)
5)
6)
1)
2)
3)
Symptom
Cannot make 
TELNET 
connection or 
cannot 
terminate the 
TELNET 
connection 
right away. 
(ping reply is 
normal).
An OK does 
not come 
back after 
login, or no 
replay comes 
back even 
after issuing a 
command.
(Some unit 
control 
commands 
are useable 
such as 
LOGOUT or 
BYE.)