IBM 5000 User Manual

Page of 204
 
 
Before You Begin
 
Table  11.  Netfinity 5000 Server Operating Specifications
Size
  – Depth: 560 mm (22.05 in.)
  – Height: 230 mm (9.06 in.)
  – Width: 420 mm (16.54 in.)
Weight
Ÿ
Typical server as shipped: 39 kg
(85.8  lb)
Environment
 
Ÿ
Air temperature:
– Server on: 10° to 35° C
(50° to 95° F)
Altitude: 0 to 914 m (3000 ft.)
– Server on: 10° to 32° C
(50° to 90° F)
Altitude: 914 m (3000 ft.) to
2133 m (7000 ft.)
– Server off: 10° to 43° C
(50° to 110° F)
Maximum Altitude: 2133 m
(7000 ft.)
 
Ÿ
Humidity:
– Server on: 8% to 80%
– Server off: 8% to 80%
 
Ÿ
Maximum altitude: 2133 m
(7000 ft)
 
Electrical Input
Ÿ
Sine-wave input (50 to 60 Hz) is
required
 
Ÿ
Input voltage:
  – Low range:
- Minimum:
90 V ac
- Maximum: 137 V ac
  – High range:
- Minimum: 180 V ac
- Maximum: 265 V ac
– Input kilovolt-amperes (kVA)
approximately:
- Minimum configuration as
shipped:  0.08 kVA
  - Maximum configuration:
0.52  kVA
Total Power Available for Drives
Ÿ
Nominal Operating Current allowed:
–  +5 V dc line: 5.3 A
–  +12 V dc line: 5.0 A
 
Heat Output
Ÿ
Approximate heat output in British
Thermal Units (Btu) per hour:
  – Minimum configuration:
350 Btu (102 watts)
  – Maximum configuration:
860 Btu (251 watts)
Acoustical Noise Emissions Values
Ÿ
Sound power, idling
– 6.2 bel for open bay system
(no hard disk drives installed)
– 6.3 bel for system with one
hard disk drive installed)
Ÿ
Sound power, operating
– 6.2 bel for open bay system
(no hard disk drives installed)
– 6.3 bel for system with one
hard disk drive installed)
Ÿ
Sound pressure, idling
– 47 dBa for open bay system
(no hard disk drives installed)
– 48 dBa for system with one
hard disk drive installed)
Ÿ
Sound pressure, operating
– 47 dBa for open bay system
(no hard disk drives installed)
– 48 dBa for system with one
hard disk drive installed)
 
   
Chapter 5. Installing a Server in a Rack Enclosure