Quattro DC Motor Side Power Convert A4 Submenu 
 
Parameter Description 
Units 
Default
Range 
Hidden
Item 
Run 
lock
out 
MAIN FAN CONTROL 
(Main Fan Control Select)  
Selects primary method of 
cooling fan control.   
−  AUTO – All cooling fans turn 
OFF after Fan Off Delay time, 
after DSPR becomes active. 
−  TEMP – Fan speed is 
responsive to highest 
measured temperature of IGBT 
modules. 
−  OFF – Manual test mode, all 
fans off 
−  LOW – Manual test mode, low 
speed 
−  MEDIUM – Manual test mode, 
medium speed 
−  HIGH – Manual test mode, 
high speed 
none Temp 
 
−  Auto 
−  Temp 
−  Off 
−  Low  
−  Medium  
−  High  
N N 
UV-ALARM LEVEL 
(Undervoltage Alarm Level) 
This parameter sets the level at 
which an under voltage alarm will 
be declared. Units in percent of L-
L voltage.  
90 
80 – 99 
Y N 
UV FAULT LEVEL 
(Undervoltage Fault Level) 
This parameter sets the level at 
which an under voltage fault will 
occur.  Units in percent of L-L 
voltage.  
80 
50 – 99 
Y N 
FLD CARRIER FRQ 
(Field Carrier Frequency)
  
Allows modification of PWM 
frequency to help eliminate 
acoustic noise. 
kHz 
3 – 10 
Y N 
Table 7: Motor Side Power Convert A4 Submenu 
 
  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 