Lucent Technologies R5SI User Manual

Page of 2643
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Routine Maintenance Procedures 
Page 5-30
Software Upgrade 
5
2. Enter 
n
 in the 
Alarm Origination 
field and press 
Enter
3. For some releases of system software, disable 
Cleared Alarm Notification
 
and 
Restart Notification
 before submitting the form.
!
CAUTION:
Disabling alarm origination prevents the system from generating 
alarms, thus preventing unnecessary trouble tickets. 
Save Announcements
1. If the system is equipped with a TN750/B Announcement circuit pack, 
enter 
display announcements
, and press 
Enter
. If administered recorded 
announcements are listed, enter 
save announcements
 [from PCSS] and 
press 
Enter. 
Where P is the port network number (1 for PPN, and 2-4 for 
EPN), C is the carrier designation (A, B, C, or D), and SS is the number of 
the slot in which the circuit pack resides (01 to 21). 
NOTE:
If multiple TN750/B circuit packs are present, you 
must
 specify the 
slot location for the save announcements command. If there is only 
one announcement circuit pack, the system defaults to the proper 
location.
NOTE:
The TN750C Announcement circuit pack contains on-board 
non-volatile memory. It is not necessary to back up a TN750C. 
Shut Down DEFINITY LAN Gateway System
If a DEFINITY LAN Gateway system resides in the control cabinet to be 
upgraded, prepare to shut down the DEFINITY LAN Gateway assembly and 
allow the disk to completely spin down. 
!
CAUTION:
Save the system parameters if you plan to reuse the current system.
!
WARNING:
Neglecting to shut down a DEFINITY LAN Gateway assembly before 
powering down the system cabinet where it resides can damage the LAN 
Gateway disk.
1. Log onto the DEFINITY LAN Gateway. 
See the DEFINITY Communications 
System Generic 3 Installation, Administration and Maintenance of 
CallVisor ASAI over the DEFINITY LAN Gateway
, 555-230-223, for the 
procedure to log on.