EXT-DEV ADMIN? Y (External Device Alarm) 
10
Duplication Interface (TN772) circuit pack in carrier (A) monitors the EXT-DEV 
alarm leads, and provides the status to the Maintenance processor (TN786B or 
TN790) in the active SPE. In the EPN the Maintenance Board (TN775) monitors 
the EXT-DEV alarm leads. The system only recognizes pairs connected to the 1M 
and 1m (ALARM MONITOR) leads. Pairs connected to the 2M, 2m, 3M, 3m, and 
3w are not recognized by the system. Refer to the 
DEFINITY Communications 
System Generic 1 and Generic 3i Wiring,
 555-204-111, for more details.
Hardware Error Log Entries and Test to Clear 
Values
NOTE:
The loss of -48 volt power will prevent detection of an external device 
alarm. AC-POWER, CARR-POW, and DC-POWER alarms could indicate the 
loss of the external device alarm -48 volt power source. ALARM-PT alarms 
may also indicate a loss of power. When analog line ports are administered 
as analog line external device alarms loss of -48 volts will prevent detection 
of an external device alarm.
Table 10-202.
Hardware Error Log Entries and Test to Clear Value
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off 
Board
Test to Clear Value
0
0
Any
Any
Any
test eda-external-device-alrm 
physical location r 2 or 6
1 or 5
Any
External Device 
Alarm Test (#120)
Any
OFF
test eda-external-device-alrm 
physical location r 2 or 6