Maintenance Object Repair Procedures 
Page 10-1171
PR-MEM (TN790 RISC Memory) 
10
Memory Functional Test (#332)
This test is destructive.
This test ensures that every DRAM memory location can be accessed and 
changed independently. Running this test wipes out all data in DRAM memory. 
This test is performed during a 
reset system 4
 or 
reset system 5
. If the test fails 
during a 
reset system
 command, refer to the "Procedure for SPE-Down Mode" in 
the 
 for the recommended maintenance 
strategy. This test can be run as a long demand test on the standby SPE.
Table 10-354.
TEST #87 Memory Parity Error Detection Test
 
Error 
Code
Test 
Result
Description/ Recommendation
100
ABORT
The test did not complete within the allowable time period.
1. Retry the command.
1029 
2014 
2015 
2016 
2017 
2018 
2020 
2022 
2024 
2025 
2051
ABORT
Refer to STBY-SPE Maintenance documentation for a description of these 
error codes.
2500
ABORT
Internal system error
1. Retry the command.
1 - 7
FAIL
The parity detection circuitry is not working correctly. If the system can 
still provide service, this indicates that the Processor circuit pack has a 
problem but can still function.
1. The TN790 Processor circuit pack should be replaced. The failure is 
identifying the PROCR as being bad and only the PROCR circuit 
pack needs to be replaced.
PASS
The parity detection circuitry is working.