DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Commands and Trouble-Clearing Aids 
Page 8-63
change system-parameters maintenance 
8
Scheduled Maintenance
A series of maintenance tests and operations runs automatically every day 
according to the schedule and settings specified in the following fields
Table 8-1.
Scheduled Maintenance Settings 
Start Time
The hour and minute in 24-hour notation at which daily scheduled 
maintenance will begin running. (22:00)
Stop Time
The hour and minute when scheduled daily maintenance will stop 
running. If any daily maintenance operations are not completed by this 
time, the system will note where in the sequence it stopped and 
perform those operations during the next scheduled daily 
maintenance.
Daily 
Maintenance
This display-only field simply represents the series of tests that are 
always run by maintenance software as part of daily maintenance.
Save 
Translation
This field indicates on which days translation data in memory will 
automatically be saved to the Mass Storage System disk and/or tape 
devices during scheduled maintenance. The save operation is first 
made to disk, followed by a disk backup to tape. On systems with 
duplicated SPEs, translation data is saved on both SPEs. Valid entries 
are 
daily
, days of the week, or 
no
. "No" specifies that no automatic 
saves are to be executed.
Control 
Channel 
Interchange
Each port network has a pair of TDM busses called A and B, each of 
which has a set of time slots dedicated to use by the control channel. 
At any one time, the control channel in each PN is carried on only one 
of the two busses. This field indicates on which days the control 
channel in each port network will be switched from one of the paired 
TDM busses to the other. Valid entries are 
daily
, days of the week, or 
no
. "No" specifies that no interchange be executed. (no)
System 
Clocks 
Interchange
On High and Critical Reliability systems, this option causes a 
Tone-Clock interchange in each port network with duplicated 
Tone-Clock circuit packs. Each port network interchanges into the 
standby Tone-Clock for 20 seconds and then back to the Tone-Clock 
that was originally active. This field indicates on which days the 
interchanges are to take place. Valid entries are daily, days of the 
week, or no. "No" specifies that interchanges be executed. (no)
The system performs a Tone-Clock interchange, making the stand by 
Tone-Clock active. The newly active Tone-Clock circuit pack is tested 
and, while active, provides system clocks for the port network in which 
it resides. The system then interchanges back to the originally active 
Tone-Clock circuit pack. 
Continued on next page