Lucent Technologies R5SI User Manual

Page of 2643
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Commands and Trouble-Clearing Aids 
Page 8-142
display system-parameters maintenance 
8
Output
An input form is displayed with the following fields. Defaults for data entry fields 
are listed in parentheses.
Product Identification
This is a 10-digit number starting with 1 that identifies the switch 
to an Operations Support System (OSS), for example, INADS.
First OSS Telephone 
Number
The first telephone number that the switch uses to report alarms 
to, for example, INADS or Trouble Tracker. The number must be 
obtained from the National Customer Support Center (NCSC) or 
the TSC. 
#
 and 
*
 are not allowed in the telephone number.
Abbrev Alarm Report
Enables the Abbreviated Alarm Report feature for the first OSS. 
(yes)
Second OSS 
Telephone Number
The second telephone number that the switch uses to report 
alarms to, for example, INADS or Definity SNMP. The number 
must be obtained from the National Customer Support Center 
(NCSC) or the TSC. 
#
 and 
*
 are not allowed in the telephone 
number.
Abbrev Alarm Report
Enables the Abbreviated Alarm Report feature for the second 
OSS. (no)
Alarm Origination to 
OSS Numbers
Indicates one of four options for alarm origination (neither):
If “both,” all Major and Minor alarms result in an automatic 
call to both OSS telephone numbers. Both OSS telephone 
numbers must be administered.
If “first-only,” all Major and Minor alarms result in an 
automatic call to the first OSS number only. The switch does 
not call the second OSS telephone number even if the 
number is administered. The first OSS telephone number 
must be administered
If “neither,” alarm origination does not take place. Warning 
alarms are not reported to either numbers.
If “second-as-backup,” all Major and Minor alarms result in 
an automatic call to the first OSS telephone number. If 
calling the first OSS telephone number fails four attempts, 
the switch starts to call the second OSS telephone number 
as a backup until calling the first OSS telephone number 
becomes successful. Both OSS telephone numbers must be 
administered.
Before Release 5, the name of this field is “Alarm Origination 
Activated.” If Alarm Origination is deactivated, both Cleared 
Alarm Notification and Restart Notification are disabled, even 
though they may still be activated in the administration.