Lucent Technologies R5SI User Manual
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Commands and Trouble-Clearing Aids
Page 8-675
test tone-clock
8
Defaults
The default for the command is short with a repeat of 1.
Parameters
Help Messages
If the system technician presses
HELP
after entering "test tone-clock" the following
message will be displayed:
Enter [[cabinet(1-3)];carr(A-B)],[’long’ or ’short’],
[’repeat’ (1-100) or ’clear’], [’schedule’]
Error Messages
If an identifier greater than 3 (three) characters is entered, or the cabinet entered
is not a digit (number), the following message will be displayed:
is not a digit (number), the following message will be displayed:
Identifier invalid
If the carrier entered is invalid, the following message will be displayed:
location
A "location" represents the physical position of the tone/clock to be
tested and is entered as "UUc" where "UU" represents the cabinet
number, and "c" represents the carrier. A cabinet number (1 - 3) may
be entered with or without a leading zero (0).
tested and is entered as "UUc" where "UU" represents the cabinet
number, and "c" represents the carrier. A cabinet number (1 - 3) may
be entered with or without a leading zero (0).
short
This will cause the command to execute a series of nondestructive
diagnostic tests.
diagnostic tests.
long
This will execute a more comprehensive and longer version of the
diagnostic tests. This may involve both destructive and nondestructive
tests.
diagnostic tests. This may involve both destructive and nondestructive
tests.
repeat number
The "number" specifies how many times each test in the sequence is to
be repeated. "Number" may be any integer between 1 and 100.
be repeated. "Number" may be any integer between 1 and 100.
clear
This option causes the test sequence (short or long) to repeat until the
alarm (if one exists against the tone clock circuit pack) is cleared or a
single test in the sequence fails. If no alarms are registered against the
tone clock circuit pack then the test sequence will be exercised only
once. The long clear option forces a clear of all alarms if no errors are
encountered during testing. The short clear option only clears alarms
pertinent to tests in the short sequence.
alarm (if one exists against the tone clock circuit pack) is cleared or a
single test in the sequence fails. If no alarms are registered against the
tone clock circuit pack then the test sequence will be exercised only
once. The long clear option forces a clear of all alarms if no errors are
encountered during testing. The short clear option only clears alarms
pertinent to tests in the short sequence.
schedule
When the "schedule" option is specified, the command is validated
and then a scheduling form is displayed to allow the technician to
schedule execution of the command. The command is then placed in
the command queue and is executed at the specified time. The
information displayed by the command is sent to the system printer
instead of the screen. Refer to the Report Scheduler and System
Printer feature specification [1] for more details.
and then a scheduling form is displayed to allow the technician to
schedule execution of the command. The command is then placed in
the command queue and is executed at the specified time. The
information displayed by the command is sent to the system printer
instead of the screen. Refer to the Report Scheduler and System
Printer feature specification [1] for more details.