PMAC2A PC104 Hardware Reference Manual 
 
Software Setup
 
26 
In order to properly setup the digital outputs an initialization PLC must be written scanning through once 
on power-up/reset, then disabling itself: 
OPEN PLC1 CLEAR 
M32=$FF 
;BITS 0-8 are assigned as output 
M34=$0 
;BITS 9-16 are assigned as input 
M40=$FF00 
;Define inputs and outputs voltages 
M42=$FFFF 
;All lines are I/O type 
DIS PLC1 
;Disable PLC1 (scanning through once on  
 ;power-up/reset) 
CLOSE 
Note: 
After loading this program, set I5=2 or 3 and ENABLE PLC 1.  
Acc-2P with Jumper E5 in Position 2-3 
M0->Y:$C0C0,0 
; Digital Output M00 
M1->Y:$C0C0,1 
; Digital Output M01 
M2->Y:$C0C0,2 
; Digital Output M02 
M3->Y:$C0C0,3 
; Digital Output M03 
M4->Y:$C0C0,4 
; Digital Output M04 
M5->Y:$C0C0,5 
; Digital Output M05 
M6->Y:$C0C0,6 
; Digital Output M06 
M7->Y:$C0C0,7 
; Digital Output M07 
M8->Y:$C0C0,8 
; Digital Input MI0 
M9->Y:$C0C0,9 
; Digital Input MI1 
M10->Y:$C0C0,10 
; Digital Input MI2 
M11->Y:$C0C0,11 
; Digital Input MI3 
M12->Y:$C0C0,12 
; Digital Input MI4 
M13->Y:$C0C0,13 
; Digital Input MI5 
M14->Y:$C0C0,14 
; Digital Input MI6 
M15->Y:$C0C0,15 
; Digital Input MI7 
M32->X:$C0C0,0,8 
; Direction Control (1=output,  0 = input) 
M34->X:$C0C0,8,8 
; Direction Control (1=output,  0 = input) 
M40->X:$C0C4,0,24 
; Inversion control (0 = 0V, 1 = 5V) 
M42->Y:$C0C4,0,24 
; JI/O port data type control (1 = I/O) 
In order to properly setup the digital outputs, an initialization PLC must be written scanning through once 
on power-up/reset, and then disabling itself: 
OPEN PLC1 CLEAR 
M32=$FF 
;BITS 0-8 are assigned as output 
M34=$0 
;BITS 9-16 are assigned as input 
M40=$FFFF 
;Define inputs and outputs voltages 
M42=$FFFF 
;All lines are I/O type 
DIS PLC1 
;Disable PLC1 (scanning through once on  
 ;power-up/reset) 
CLOSE 
Note: 
After loading this program, set I5=2 or 3 and ENABLE PLC 1.