CHAPTER 6 M600 Main Cabinet
Installation specifications
Table 6.5
Installation Specifications of M600 Main Cabinet (1)
Item
Specification
Mass
Up to 250kg (approx.552 lb) (*1)
Power condition
Input voltage
Single phase
 100 to 120 VAC
(+-10%) 
Single phase
 200 to 240 VAC
(+-10%) 
Input frequency
50/60 Hz (+2 to -4%)
Maximum consumption current
13.4 A
Leakage current  (1 for each cable)
2.2 mA or less
6.6 A
4.7 mA or less
Ground resistance
100ohm or less ( class C installation standard)
Temperature condition Operating
5 to 35 degrees Celsius (+41 to +95 F) (*2)
Not operating
0 to 50 degrees Celsius (+32 to +122F)
Humidity condition
Operating
20 to 80%RH (no condensation)
Not operating
8 to 80% RH (no condensation)
Vibrations condition
Operating
0.2 G
Idle
0.4 G
Noise
55 db (A) (*3)
Installation
Floor Stand type
*1:
The mass shows M600 main cabinet without Expansion File Units.
*2:
If the ambient temperature exceeds 35 degrees Celsius (+95 F) during operation, a
warning message is output. Take steps to rectify the problem immediately.
*3:
The indicated noise is the mean value of the measurements obtained in an anechoic
chamber with less echoic influence. The actual noise measured at the installation site
may be greater than the indication noise due to surrounding noise and echoes.
78