Fujitsu GranPower7000 (GP 7000F) User Manual

Page of 199
12.1 UPS Control Interface
*BPS
*BTL
*UPSON
*ACOFF
SG
ER
BPS
BTL
UPSON
ACOFF
SG
ER
GP 7000
Interface cable
UPS
6
7
8
9
5
1
Figure 12.1
Signal Configuration
Electrical requirements:
The UPS control interface must meet the following electrical requirements:
Table 12.2
Input Circuits
       Signal names                                                     Input conditions                                    
*BPS                                
                                                      
*BTL                               
                                                      
*UPSON                          
                                                      
*ACOFF                                                                    
                                          * Dead-front relay contacts                           
                                          * Contact rating:  12 V DC, 10 mA or more             
                                          * Gold plated contacts or lead relays are recommended.
                                                                 
Table 12.3
Output Circuits
        
ER                                      Output voltages  
                                           Output currents 
        
                                                                                                   3.76 V to 5.5 v       
                                                                                                   0. to 0.4 v           
                                                                                                   max. -4 mA            
                                                                                                   max. 4 mA             
        Signal names                                           Output conditions                               
                                                                                    VOH 
                                      
                                                                                    VOL 
                    
                                                                                     IOH 
                                      
                                                                                     IOL 
Signal Cables
Use shielded pair cables that meet the following specifications.
Connector shapes:
D-SUB 9-pin, Male connector (Female connector on the equipment side)
DEU-9PF-FO (Manufactured by Japan Aircraft Electronics Inc.) or equivalent
Cable length:
10 m or less
DC resistance:(per pair, both ways)
400 ohm/km or less
147