Omron C200HE User Manual
365
6-2-1 PC with I/O Units Only
Here, we’ll compute the cycle time for a simple PC. The CPU Unit controls only
I/O Units, eight on the CPU Rack and five on a 5-slot Expansion I/O Rack. The
PC configuration for this would be as shown below. It is assumed that the pro-
gram contains 5,000 instructions requiring an average of 0.156
I/O Units, eight on the CPU Rack and five on a 5-slot Expansion I/O Rack. The
PC configuration for this would be as shown below. It is assumed that the pro-
gram contains 5,000 instructions requiring an average of 0.156
µ
s each to
execute.
CPU Rack
Expansion I/O Rack
12-point Output Units
8-point Output Unit
16-point Input Units
8-point Input Units
8-point Output Units
Calculations
The equation for the cycle time from above is as follows:
Cycle time =
Overseeing time + Program execution time + I/O refresh time +
Peripheral device servicing time
Peripheral device servicing time
Process
Calculation
With Peripheral
Device
Without
Peripheral Device
Overseeing
Fixed
0.7 ms
0.7 ms
Program execution
0.156
µ
s/instruction
×
5,000 instructions
0.78 ms
0.78 ms
I/O refresh
See below.
0.34 ms
0.34 ms
Peripheral device
servicing
servicing
Minimum time
0.26 ms
0.0 ms
Cycle time
Total of above
2.08 ms
1.82 ms
The I/O refresh time would be as follows for two16-point Input Units, four 8-point
Input Units, two 12-point Output Units (12-point Units are treated as 16-point
Units), and five 8-point Output Units controlled by the PC:
Input Units, two 12-point Output Units (12-point Units are treated as 16-point
Units), and five 8-point Output Units controlled by the PC:
8 pts
(16 pts
×
2) + (8 pts
×
4)
×
20
µ
s = 0.34 ms
×
20
µ
s +
8 pts
(16 pts
×
2) + (8 pts
×
5)
6-2-2 PC with Host Link and Remote I/O Master Units
Here, the cycle time is computed for a PC with a Host Link Unit and Remote I/O
Master Unit installed. The PC configuration for this could be as shown below.
Master Unit installed. The PC configuration for this could be as shown below.
The CPU Unit controls three 8-point Input Units, three 8-point Output Units, a
Host Link Unit, and a Remote I/O Master Unit connected to a Remote I/O Slave
Rack containing four 16-point Input Units and four 12-point Output Units.
Host Link Unit, and a Remote I/O Master Unit connected to a Remote I/O Slave
Rack containing four 16-point Input Units and four 12-point Output Units.
Calculating Cycle Time
Section 6-2