Response Format
@
R
E
x 10
1
x 10
0
x 16
1
x 16
0
x 16
3
x 16
2
x 16
1
x 16
0
FCS
Node no.
End code
Header
code
Read data (1 word)
Read data (for number of words read)
Terminator
Limitations
The text portion of the response’s first frame can contain up to 30 words. If more
than 30 words are read, the data will be returned in multiple frames.
In the second and later frames, the text portion of the response can contain up to
31 words.
If a valid bank number is specified but the PC isn’t equipped with that EM bank,
“0000” will be returned as the read data.
This command can’t be used to change the current bank number.
The INITIALIZE and ABORT commands can be sent instead of the delimiter for
multiple responses for this command. If other commands are sent, they will be
treated the same as delimiters.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
OK
OK
OK
OK
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
OK
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect and an end code of 15 (entry number data error) will be returned if the
specified words exceed the data area boundaries, the specified words aren’t
specified in BCD, or an invalid bank number is specified.
End code
Contents
00
Normal completion
13
FCS error
14
Format error
15
Entry number data error
18
Frame length error
A3
Aborted due to FCS error in transmit data
A8
Aborted due to frame length error in transmit data
10-3-9 IR/SR AREA WRITE –– WR
Writes data to the IR and SR areas, starting from the specified word. Writing is
done word by word.
Command Format
@
W
R
FCS
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
x 16
3
x 16
2
x 16
1
x 16
0
Node no.
Header
code
Beginning word
(0000 to 0511)
Write data (1 word)
Write data 
(for number of words to write)
Terminator
Host Link Commands