497
Response Format
,
@
Q
Q
x 10
0
x 10
1
x 16
1
x 16
0
I
R
x 16
3
x 16
2
x 16
1
x 16
0
ON/
OFF
x 10
3
x 10
2
x 10
1
x 10
0
ON/
OFF
Node no.
Header
code
Sub-header
code
End code
Timer/Counter
If PV is specified the sta-
tus of the Completion Flag
is also returned.
Data break
Bit data
ON/OFF
Word data
IR, SR, LR, HR,
AR, DM
Terminator
FCS
,
,
,
Limitations
The data is read in the same order in which it was registered with QQMR.
A response of “0000” will be returned for non-existent words such as DM 6656 to
DM 6999, unallocated expansion DM, or non-existent EM banks.
The INITIALIZE and ABORT commands can be sent instead of the delimiter for
multiple responses for this command. If other commands are sent, they will be
treated the same as delimiters.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
OK
OK
OK
OK
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
OK
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
An end code of 19 (not executable) will be returned if there is no registered data.
End code
Contents
00
Normal completion
13
FCS error
14
Format error
18
Frame length error
19
Not executable
A3
Aborted due to FCS error in transmit data
A8
Aborted due to frame length error in transmit data
10-3-37
ABORT –– XZ
Aborts the Host Link command that is currently being processed, allowing the
next command to be received. The ABORT command does not receive a re-
sponse.
Command Format
@
X
Z
x 10
0
x 10
1
Node no.
Header
code
Terminator
FCS
Host Link Commands
Section 10-3