3-5-2 Slave Rack Error Flags
AR bits 0200 to AR 0204 correspond to the unit numbers of Remote I/O Slave
Units #0 to #4. These flags will turn ON if the same number is allocated to more
then one Slave or if a transmission error occurs when starting the System. Refer
to SR 251 for errors that occur after the System has started normally.
3-5-3 Group-2 Error Flags
Bits AR 0205 to AR 0215 correspond to Group-2 High-density I/O Units and B7A
Interface Units 0 to 9 (I/O numbers) and will turn ON when the same number is
set for more than one Unit, when the same word is allocated to more than one
Unit, when I/O number 9 is set for a 64-point Unit, or when the fuse burns out in a
Transistor High-density I/O Unit. AR bit 0215 will turn ON when a Unit is not rec-
ognized as a Group-2 High-density I/O Unit.
Note Bits SR 28000 to SR 28015 also act as Error Flags for Group-2 High-density I/O
Units with unit numbers 0 to F.
3-5-4 Optical I/O Unit and I/O Terminal Error Flags
AR 03 through AR 06 contain the Error Flags for Optical I/O Units and I/O Termi-
nals. An error indicates a duplication of a unit number. Up to 64 Optical I/O Units
and I/O Terminals can be connected to the PC. Units are distinguished by unit
number, 0 through 31, and a letter, L or H. Bits are allocated as shown in the fol-
lowing table.
Bits
AR03 
allocation
AR04 
allocation
AR05 
allocation
AR06 
allocation
00
0 L
8 L
16 L
24 L
01
0 H
8 H
16 H
24 H
02
1 L
9 L
17 L
25 L
03
1 H
9 H
17 H
25 H
04
2 L
10 L
18 L
26 L
05
2 H
10 H
18 H
26 H
06
3 L
11 L
19 L
27 L
07
3 H
11 H
19 H
27 H
08
4 L
12 L
20 L
28 L
09
4 H
12 H
20 H
28 H
10
5 L
13 L
21 L
29 L
11
5 H
13 H
21 H
29 H
12
6 L
14 L
22 L
30 L
13
6 H
14 H
22 H
30 H
14
7 L
15 L
23 L
31 L
15
7 H
15 H
23 H
31 H
Optical I/O Unit and I/O
Terminal Error Flags
AR (Auxiliary Relay) Area
Section 3-5