Omron C200HE User Manual

Page of 564
67
Word(s)
Default
Function
Bit(s)
DM 6556
00 to 07
Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
1.2 K
08 to 15
Frame format
Start
Length
Stop
Parity
00: 
1 bit
7 bits
1 bit
Even
01: 
1 bit
7 bits
1 bit
Odd
02: 
1 bit
7 bits
1 bit
None
03: 
1 bit
7 bits
2 bit
Even
04: 
1 bit
7 bits
2 bit
Odd
05: 
1 bit
7 bits
2 bit
None
06: 
1 bit
8 bits
1 bit
Even
07: 
1 bit
8 bits
1 bit
Odd
08: 
1 bit
8 bits
1 bit
None
09: 
1 bit
8 bits
2 bit
Even
10: 
1 bit
8 bits
2 bit
Odd
11: 
1 bit
8 bits
2 bit
None
1 start bit, 7-bit
data, 1 stop bit,
even parity
DM 6557
00 to 15
Transmission delay 
0000 to 9999: BCD in 10-ms units.
0 ms
DM 6558
00 to 07
Node number (Host Link)
00 to 31 (BCD)
0
08 to 11
Start code enable (RS-232C)
0: Disable; 1: Set
Disabled
12 to 15
End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
Disabled
DM 6559
00 to 07
Start code (RS-232C)
00 to FF (binary)
0000
08 to 15
12 to 15 of DM 6558 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6558 set to 1:
End code (RS-232C)
00 to FF (binary)
3-6-6 Special I/O Unit Area Settings
The setting in bits 08 through 15 of DM 6602 determines the size and location of
the Special I/O Unit Area, as shown in the following table.
Setting
Mode
Function
00
C200H-compatible
RAM Mode
DM 1000 through DM 2599 are used for the Special I/O Unit Area.
Data in the Special I/O Unit Area can be read/written.
The data cannot be converted to ROM.
01
C200H-compatible
ROM Mode 1
The contents of DM 7000 through DM 7999 are transferred to DM 1000 through DM 1999
at startup and DM 1000 through DM 1999 are used for the Special I/O Unit Area.
The UM Area Allocation operation must be performed beforehand.
The data is compatible with C200H applications that use EEPROM/EPROM.
ROM conversion is possible indirectly by converting DM 7000 through DM 7999 to ROM.
02
DM Linear Mode 1
DM 7000 through DM 7999 are used for the Special I/O Unit Area.
The UM Area Allocation operation must be performed beforehand.
DM 1000 through DM 1999 can be used as regular DM.
DM 7000 through DM 7999 can be converted to ROM.
DM (Data Memory) Area