SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
Pa
ra
m
e
te
rs
Parameter Reset Features 
On initial power up, all parameters are at original values. In many cases, when a 
Parameter Value is altered, associated Parameter Values are automatically altered 
accordingly. 
To return an operator adjusted Parameter Value to the preset value, with the appropriate 
Index and Parameter Number displayed, press 
,
 . 
To reset all parameters to preset 
values, refer to Master Reset (P999) on page 84. 
Programming Security 
All operator programming is retained in non-volatile memory, immune to power 
interruptions. When programming is complete, the programmer may be removed and 
locked away to prevent inadvertent programming alteration. As well the Lock (P000) 
parameter may be used. 
P000 Lock
Secures the SITRANS LU01 from changes
Access this parameter directly (type 000) and enter any value (except 1954) to secure 
programming lock. To remove the programming lock, access this parameter and enter 
1954
. You cannot scroll to this parameter.
Note:
Perform a Master Reset (P999) if the SITRANS LU01 was 
bench tested 
using 
arbitrary Parameter Values before system installation, following an EPROM 
replacement, or whenever complete reprogramming is required. 
Values
1954
*
OFF (programming permitted)
-1
Simulation Controls (relays energize based on simu-
lated level)
other
lock activated (programming secured)
WARNING: Use this lock as backup security only. It uses a fixed 
value which can be discovered by unauthorized personnel.