A-2 Appendix
MN850
Using CE approved components will not guarantee a CE compliant system!
1.
The components used in the drive, installation methods used, materials
selected for interconnection of components are important.
2.
The installation methods, interconnection materials, shielding, filtering and
grounding of the system as a whole will determine CE compliance.
3.
The responsibility of CE mark compliance rests entirely with the party who
offers the end system for sale (such as an OEM or system integrator).
Baldor products which meet the EMC directive requirements are indicated with a “CE” mark. A duly
signed CE declaration of conformity is available from Baldor.
T1 T2
L1
AC Main 
Supply
Four Wire
“Wye”
L1
L2
L3
L2 L3
T3
Route all power wires
L1, L2, L3 and Earth
(Ground) together in
conduit or cable.
Note:
Wiring shown for clarity of
grounding method only.
Not representative of actual
terminal block location.
Control
Note:
Use shielded cable for control signal wires.  Route
control signal wires in conduit.  These wires must be
kept separate from power and motor wires.
PE
 
Enclosure Backplane (see Section 2)
Motor 
GND
All shields
PE