Baldor Baldor User Manual

Page of 70
Operation 3-9
MN850
Keypad Starting and Running the Motor in Optimise Mode
Action
Description
Display
Comments
Apply Control Voltage
(115VAC)
Keypad Display shows this
opening message.
Baldor Soft Start
Logo display for 2 seconds.
If no faults the display will show
this message.
Stopped & Ready
System Status mode.
Press ENTER key
APPLICATIONS
AUTO FEATURES
Press ENTER key
Access Level 1 Application Menu.
Settings
Default (Keypad)
Press 
 key two times
Scroll to the correct application.
Small Pump
Large Pump
Press ENTER key
Select the application.
Large Pump
Conveyor
Large pump is selected in this
example.
Press ENTER key
Choose set of parameters for the
application.
Send to Store
’#’=no Enter=Yes
Press ENTER key
Scroll to the PASSWORD menu.
Storing
Press # key twice
Press # key two times to exit
programming.
Large Pump
Conveyor
Press Start/Stop key
Displays motor starting current
and full voltage and current.
Starting
Current
8A
Full volts
Current
8A
Press OPTIMISE key
Optimising
Current
4A
Ready for Remote Start/Stop.
Baldor Digital Soft–Start offers three modes of protection during operation:
1.
Full protection with full voltage after top of ramp.
2.
Full optimize protection with energy optimizing by reduced voltage at lower
loads.
3.
Start + Bypass protection (during start only).  No soft–start protection is
provided when during bypass (when soft–start is shorted by the bypass
contactor).
Remote Start and Running the Motor
When Remote Starting is selected, the keypad Start/Stop pushbutton is not active.
Action
Description
Display
Comments
Apply 115VAC at the
input terminals S0 and
S1.
Input 1 is Start/Stop input when
Remote Starting is selected.
(P52 Bit 16 set to terminal.)