Example:
 
  An enclosure that requires 30 VA and is installed 94 feet (28 m) from the transformer 
would require a minimum wire gauge of 20 AWG.
 
NOTE:
 
  Distances are calculated in feet; values in parentheses are meters.
 
Table A.  
 
24 VAC Wiring Distances
 
The following are the recommended maximum distances for 24 VAC applications and are calculated with 
a 10 percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for 
AC-powered devices.
 
Wire Gauge
20
18
16
14
12
10
Total V
A
 consumed
10
 
283 (86)
451 (137)
716 (218)
1142 (348) 1811 (551) 2880 (877)
 
Maximum distance from 
transformer to load
20
 
141 (42)
225 (68)
358 (109)
571 (174)
905 (275)
1440 (438)
 
30
 
94 (28)
150 (45)
238 (72)
380 (115)
603 (183)
960 (292)
 
40
 
70 (21)
112 (34)
179 (54)
285 (86)
452 (137)
720 (219)
 
50
 
56 (17)
90 (27)
143 (43)
228 (69)
362 (110)
576 (175)