Bosch D5500CU User Manual

Page of 78
RPS
 RPS Operation and Control Panel Account Notes | en
71
Bosch Security Systems, Inc.
Installation Guide
4998141259 | 12 | 2011.10
7.2
Control Panel Account Notes
7.2.1
2000 Series
RAM II Exporter version 004 does not import account notes and zone notes. The fields for 
these notes are empty in RPS.
7.2.2
D6412/D4412 and DS7240/DS7220
Changing an RF ID: RPS allows you to change the RF ID for a location without resetting 
the learned characteristics for the transmitter. For example, the control panel supervises 
an RF3401 (RF3401E) Point Transmitter. The control panel learned that both the reed 
switch or magnet, and the sensor loop, are in use. The magnet must be in place and the 
sensor loop must be normal for the transmitter to be normal (not faulted). If you enter an 
ID for a new transmitter at this location, the control panel expects to see both the reed 
switch and the sensor loop normal before the zone state is declared normal. To only use 
the reed switch (or only the sensor loop), remove the ID for the location at a keypad by 
using the Installer RF Menu. Refer to the control panel's documentation for instructions.
Parameters Changed Report: If changes are made to the control panel's programming 
using RPS and the remote programming session ends with the Reset Panel box checked, 
the control panel does not send a Parameters Changed report. If the session ends and 
the Reset Panel box is not checked, the control panel sends the Parameters Changed 
report.
Miscellaneous System Trouble Options: The Enable AC Fail Trouble Tone and Enable 
Ground Fault Display and Trouble Tone options, located in the Miscellaneous category in 
RPS, are only available on control panels with firmware version 1.04 or greater.
Output Function Types: If Output Function Types 1,8 to 1,13 and 2,11 are assigned to an 
output, you should not be able to turn the output on or off or toggle it in RPS; however, 
the control panel does not force some of these restrictions when using RPS.
Bypassing Unbypassable Zones in RPS: Some zones that are not bypassable at the 
control panel might be bypassable in RPS.
Unbypassing a zone from RPS does not reactivate Zone: Unbypassing a zone from RPS 
does not return the zone to active status, allowing it to generate an alarm response if 
violated. To return the zone to active status from RPS:
Disarm the area in which the zone is assigned.
Unbypass the zone.
Rearm the area.
Arming States in Diagnostics: The control panel does not allow RPS to change arming 
states to a lower state without first disarming the control panel. For example, if the 
control panel is All On, you cannot switch to Perimeter Only until you disarm the control 
panel and rearm Perimeter Only. You can switch to a higher arming state (Perimeter Only 
to All On) without first disarming the control panel.
Callback: Initiate callback immediately to ensure proper callback operation. Click Yes at 
the prompt to make RPS automatically detect the phone ring. This feature might not work 
with certain modems.
RF Jam Detect not shown in Diagnostics: RPS does not indicate if the RF receivers are 
jammed in Diagnostics. RF Receiver status is shown as either "Off Normal" or "Missing." 
No other trouble conditions appear.
Non-traditional Alphabetical Characters Not Supported by RPS (DS7240-SWE, DS7240-
NOR only): Characters that are not part of the Swedish or Norwegian alphabet, but are 
supported by the control panel, cannot be entered into RPS. These characters do not 
appear if they are sent to RPS from the control panel.