Environmental Monitoring Unit: User’s Guide
24
Managing the Unit with SNMP
Using the OIDs
Using monitoring 
OIDs
Use the read-only
 
[mUpsEnviron]
 
OID
s to view temperature and 
humidity values.
Using contact OIDs
Use the 
[mUpsContact]
 
OID
s to view and configure the current contact 
sensor values.
OID
OID
OID
OID
Function
Function
Function
Function
mUpsRelativeHumidity
Reports the relative humidity sensed by the probes.
mUpsAmbientTmperature
Reports the ambient temperature in Celsius, sensed 
by the probes.
OID
OID
OID
OID
Function
Function
Function
Function
mUpsContactNumContacts
Lists how many contact sensors the unit uses.
{mUpsContactTable}
Lists the OIDs for each contact sensor: 
contactNumber
: Identifies the contact sensor for 
which the other OIDs apply.
normalState
: Defines the contact sensor’s normal 
condition (unknown, open, or closed). 
description
: Defines the purpose of the contact 
sensor
monitoringStatus
: Defines whether the contact 
sensor is being monitored
currentStatus
: Identifies the sensor’s current 
condition (unknown, noFault, or fault).