APC UPS 2200VA User Manual

Page of 3
operation 
151 - 302 V 
 
 Batteries & Runtime
 
Battery type 
Maintenance-free sealed Lead-Acid battery 
with suspended electrolyte : leakproof 
Replacement battery cartridge 
RBC43 
RBC™ Quantity 
Typical backup time 
at half load 
15.7 minutes (990 Watts) 
Typical backup time 
at full load 
5.2 minutes (1980 Watts) 
Runtime Chart
 
Smart-UPS
 
 
 Communications & Management
 
Interface port 
DB-9 RS-232, SmartSlot, USB 
Available Smart Slot Interface Quantity 
Control panel 
LED status display with load and battery bar-
graphs and On Line : On Battery : Replace 
Battery : and Overload Indicators 
Audible alarm 
Alarm when on battery : distinctive low 
battery alarm : configurable delays 
Emergency Power Off (EPO) 
Yes 
 
 Surge Protection and Filtering
 
Surge energy rating 
480 Joules 
Filtering 
Full time multi-pole noise filtering : 0.3% 
IEEE surge let-through : zero clamping 
response time : meets UL 1449 
 
 Physical
 
Maximum height 
4 inches ( 8.89 cm ) 
Maximum width 
19 inches ( 48.26 cm ) 
Maximum depth 
26 inches ( 66.04 cm ) 
Rack Height 
2 U 
Net weight 
96 lbs. ( 43.64 kg ) 
Shipping Weight 
125 lbs. ( 56.82 kg ) 
Shipping Height 
10 inches ( 25.40 cm ) 
Shipping Width 
25 inches ( 62.23 cm ) 
Shipping Depth 
39 inches ( 98.04 cm ) 
Color 
Black 
Units per Pallet 
 
 Environmental
 
Operating Environment 
0 - 40 °C ( 32 - 104 °F ) 
Operating Relative Humidity 
0 - 95 % 
Operating Elevation 
0-10000 feet ( 0-3000 meters ) 
Storage Temperature 
-15 - 45 °C ( 5 - 113 °F ) 
Storage Relative Humidity 
0 - 95 % 
Storage Elevation 
0-50000 feet ( 0-15000 meters ) 
Online thermal dissipation 
300 BTU/hr 
 
more details...
 
Topology:
 
Line Interactive 
Page 2 of 3
APC Smart-UPS 2200VA USB & Serial RM 2U 230V
9/3/2548
http://www.apcc.com/resource/include/techspec_index.cfm?base_sku=SUA2200RMI2U