Analog Input module 
 
 
2-2 ADAM 5000 IO modules User’s Manual
 
 
Analog input modules use an A/D converter to convert sensor voltage, 
current, thermocouple or RTD signals into digital data. The digital data is then 
translated into engineering units.  The analog input modules protect your 
equipment from ground loops and power surges by providing opto-isolation 
of the A/D input and transformer based isolation up to3,000 V
DC
 
 
 
2.1  ADAM-5013 3-channel RTD input module
 
The ADAM-5013 is a 16-bit, 3-channel RTD input module that features 
programmable input ranges on all channels. This module is an extremely 
cost-effective solution for industrial measurement and monitoring 
applications.  Its opto-isolated inputs provide 3,000 V
DC
 of isolation between 
the analog input and the module, protecting the module and peripherals 
from damage due to high input line voltage. 
 
Note:  Owing to the conversion time required by the A/D converter, the 
initialization time of each ADAM-5013 module is 5 seconds. Thus the 
total initialization time will be about 20 seconds if all 4 I/O slots in 
an ADAM-5000 main unit contain ADAM-5013 modules. 
 
 
 
 
 