Networking Cards
 Planning | en
9
Bosch Security System, Inc.
Installation Manual
F.01U.214.374 | 01 | 2012.08
3
Planning
3.1
General considerations
If the panel is to be used in a networked system, be careful to plan properly before installing 
any panels. Check:
whether the networked panels will be installed near each other or distributed over a 
wider area
whether or not any of the networked panels will be in different buildings
the types and numbers of Networking Cards needed
interconnection requirements, including the maximum allowable cable lengths which 
depend on the intended interconnection method (Ethernet, fiber optic cable, or wire).
For each panel, be careful to plan properly before installing any devices. Check:
the compatibility and number of devices to be connected
the battery capacity needed
the wiring requirements, including the maximum allowed cable length
the installation requirements according to this Installation and Operation Guide,NFPA 72, 
Local Codes and the Authority Having Jurisdiction (AHJ).
3.2
Ground Fault Detection
Each networking card has a specific terminal or terminals that are Ground Fault Detection 
enabled. As indicated by the checked boxes in the following table, Port 1 on all three 
networking cards is ground fault enabled; as is Port 3 on the wired card (FPE-1000-NW).
Table 3.1 Network Port Identification
For Ground Fault Detection to work properly, one and only one end of a communication 
connection (cable) joining two networking cards must be Ground Fault Detection enabled. To 
facilitate this, the wired card (FPE-1000-NW) and the fiber optics card (FPE-1000-NF) each 
have a jumper located near the back of the Ethernet IN port (Port 1 on the wired card and 
Port 3 on the fiber optic card). This jumper allows Ground Fault Detection to be disabled for 
this port. Recommended communication connection practice is to come out of one card and 
in on the next. In cases where you are switching from a wired or fber optic card to a different 
type of card, you must use the Ethernet port which should be OUT not IN which is the default. 
Move the jumper on this card so that Ground Fault Detection is disabled at this end of the 
connection (making it an Ethernet OUT). Remove the jumper from both pins and replace it on 
only one pin so that it does not get misplaced in case Ground Fault Detection needs to be re-
enabled later.
3.3
Port supervision
Each peer-to-peer connection (cable) connected to a networking card port used for panel-to-
panel communication must be supervised. This supervision is selected by programming.
For programming information, follow the panel programming instructions in the FPA-1000 
Network Quick Installation Guide
, or see Keypad Operation and Programming, Programming or 
Port
-NE
-NF
-NW
1
Ethernet IN
Ethernet IN
Wired IN
2
Ethernet OUT
Fiber IN
Wired OUT
3
Ethernet
Fiber OUT
Ethernet IN