25
Table 11: Connection Sequence – C900V2 and Generic Control Panel in Separate Enclosures
(UL Standard 864)
Seq
C900V2 Connection
Control Panel Connection
Other Connection
1
RJ-45 PANEL connector
to
RJ-45 connector (telco dialer)
2
RJ-45 ETHERNET connector
to
LAN or WAN
3
– V terminal
to
–12 to –24 VDC (common)
4
V +
to
+12 to +24 VDC output
5
Power supply +BAT input to
battery 1 + terminal
battery 1 + terminal
6
Power supply –BAT input to
battery 2 – terminal
battery 2 – terminal
7
Battery 1 – terminal to battery 2 +
terminal (in series)
terminal (in series)
8
Install an EOL resistor for the
control panel across OUT2-L
and OUT1-R
control panel across OUT2-L
and OUT1-R
9
OUT2-L to OUT1-L
10
OUT2-R to OUT1-R
11
OUT1-R
to
C900V2 enclosure closed-circuit
tamper switch
tamper switch
12
C900V2 enclosure closed-circuit
tamper switch to control panel
enclosure closed-circuit tamper
switch
tamper switch to control panel
enclosure closed-circuit tamper
switch
13
24-hour zone input common
to
Control panel enclosure closed-
circuit tamper switch
circuit tamper switch
14
OUT2-L
to
24-hour zone input
15
Battery negative input
to
Battery negative terminal
16
Battery positive input
to
Battery positive terminal
17
AC input
AC transformer
18
AC input
AC transformer
NOTE: The sequence numbers appear in the diagram in Figure 13.