Schneider Electric 66124 User Manual

Page of 98
 
 
Network Management Card & Modbus/Jbus                                                                                        34022321XT indice :AE            Page 16/98 
Network Management Teleservice Card 
                 
APC by Schneider Electric  
www.apc.com 
Ethernet port 
LED  
Colour  
Activity 
Description  
ACT  
Green  
 
Off  
 
Card not connected to the network.  
 
 
 
On  
 
Card  connected  to  the  network  but 
without activity 
 
 
 
Flashing  
 
Port 
is 
active 
in 
receiving 
/
 
transmission 
100M  
Orange  
 
Off  
 
Port operating at 10Mbits/s. 
 
 
 
On  
 
Port operating at 100Mbits/s. 
 
Service port (Settings/Sensor) 
LED  
Colour  
Activity 
Description  
UPS  
Green  
 
Off  
 
Card startup in progress.  
Data  
 
 
On  
 
Communication with UPS in progress 
 
 
 
Flashing  
 
Normal  operation.  
Communication with the UPS is 
operational 
RS232  
Orange  
 
Off  
 
Configuration menu is active 
 
 
 
On  
 
Normal 
operation. 
Configuration 
menu is deactived 
 
 
 
Flashing  
 
Communication with the Environment  
Sensor (option). 
 
Phone port 
LED  
Colour  
Activity 
Description  
UPS  
Green  
 
Off  
 
Card not connected to phone network 
Data  
 
 
On  
 
Card  connected  to  phone  network, 
but no activity 
 
 
 
Flashing  
 
Port is sending/receiving  
CD  
Orange  
 
Off  
 
Modem is not connected 
 
 
 
On  
 
Modem is connected 
 
 
 
Flashing  
 
Modem is connecting 
4.3  Installation in the UPS 
The Network Management Teleservice Card (66124) can be "hot" installed in the MGE Galaxy 7000 UPS or SSC unit. 
Note the card's MAC address prior to insertion 
Connect the ETHERNET cable 
Insert and tighten the card's retaining screws 
Wait 3 min.; the card is completely operational when the green UPS Data LED flashes continuously 
 
For Teleservice installation, the NMTC card must be installed in the SSC unit. 
4.4  Sensor installation (option) 
The Environment sensor is available as an option on the Network Management Card. SKU number is 66846. 
The sensor allows remote monitoring of the UPS's environment through regular measurements: temperature, humidity, status of two external 
contacts. It also enables notification of alarms (e-mail, trap SNMP) according to pre-programmed thresholds. 
It is connected to the Service port (Settings/Sensor) directly on the Network Management Card with a standard Ethernet cable (20 meters 
maximum). 
Recognition is automatic. Supervision and configuration are performed via a menu that can be accessed directly from the home page.