7.2  Shutdown criteria managed by the Network Management Card 
During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If several criteria are selected, (See 
page
 
Shutdown parameters), the first criterion encountered will launch the shutdown procedure. 
 
Start of the shutdown sequence 
Delay before  
shutdown 
 
Utility failure 
Remaining autonomy 
100% 
Shutdown after : 
If remaining time under 
UPS may go 
on  bypass, 
load is no more 
protected 
Card parameters 
UPS parameters 
Shutdown duration 
Battery 
autonomy 
ratio 
0% 
Shutdown if 
remainig time 
ratio  under 
 
 
7.2.1  Backup time before initiating the shutdown procedure (Shutdown After - Shutdown 
Timer) 
When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown 
procedure at the end of the countdown. 
This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery backup time. 
 
Note 1: 
The Network Shutdown Module can also manage its own Shutdown Timer (configurable in the Shutdown Module"set-up" menu of each Network 
Shutdown Module) launched when the UPS switches to battery.  
Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is not guaranteed (e.g. power 
restoration if only this system was shut down).