Schneider Electric 66124 User Manual

Page of 98
 
 
Network Management Card & Modbus/Jbus                                                                                        34022321XT indice :AE            Page 72/98 
Network Management Teleservice Card 
                 
APC by Schneider Electric  
www.apc.com 
10.1.3 Configuration of the JBUS/MODBUS communication parameters  
Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600 baud, 8 bits, no parity, 1 stop 
bit, and without flow control. 
Check that UPS power is on. 
Enter the MGEUPS or mgeups password (non modifiable). 
 
The next menu appears: 
 
----------------------------------------------------------------------------- 
MGE UPS SYSTEMS 
NETWORK MANAGEMENT CARD 
----------------------------------------------------------------------------- 
        1 : Reset 
        2 : Network configuration 
        3 : Set Login Password to Default 
        4 : Return to Default Configuration 
        5 : Jbus configuration 
        6 : Sensor configuration 
        0 : Exit 
----------------------------------------------------------------------------- 
 
Type 5 and return to display the JBUS configuration menu. 
 
The next menu appears: 
 
----------------------------------------------------------------------------- 
Jbus settings 
----------------------------------------------------------------------------- 
        1 : Display Jbus settings 
        2 : Modify Jbus settings 
        3 : Display Jbus diagnostics 
        4 : Reset Jbus diagnostics 
        5 : Return to Jbus Default Configuration 
        6 : Display Jbus frames 
        0 : Exit 
-----------------------------------------------------------------------------