Schneider Electric 66124 User Manual

Page of 98
 
 
Network Management Card & Modbus/Jbus                                                                                        34022321XT indice :AE            Page 88/98 
Network Management Teleservice Card 
                 
APC by Schneider Electric  
www.apc.com 
10.3.4.8 UPS running Power Saving Mode 
Status 
Modbus 
Address 
(word + 
bit) 
Value 
  
  
  
  
  
Main UPS status 
  
  
  
Load Powered 
400 
Load on inverter 
401 
UPS on battery 
404 
Load on AC Bypass 
407 
UPS in maintenance position 
461 
Battery Charging 
493 
UPS in Power Saving Mode 
Nota: Available with NMC fw 808 and G7000 package AM
 
41B 
Breaker status 
  
  
Q5N circuit breaker 
47B 
Q1 circuit breaker 
443 
Q4S circuit breaker 
46E 
 
QF1 circuit breaker 
42F 
  
Q3BP circuit breaker 
416 
  
UPS Fault 
  
  
  
UPS general alarm - Red Led from UPS HMI 
Nota: Available with NMC fw 808 and G7000 package AN
 
402 
  
Load not protected 
41A 
  
UPS Internal Communication Fault 
409 
  
Rectifier fault 
419 
  
Rectifier (PFC) fuse fault 
449 
  
Battery temperature fault 
42A 
  
End of battery runtime 
406 
  
Emergency Power Off 
40B 
  
Fan Faillure 
40E 
  
UPS Warning 
  
  
  
Orange Led from UPS HMI 
Nota: Available with NMC fw 808 and G7000 package AN
 
41C 
  
Overload 
40A 
  
Low Battery Warning 
405 
  
Inverter Overload 
4C2 
  
Static switch overload 
465 
  
AC Normal Frequency Out Of Tolerance 
44B 
  
AC Normal Voltage Out Of Tolerance 
448 
  
AC bypass Out of tolerance 
467