11.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11) 
SNMP traps are sent when alarms appears and desappears. 
Level : 1:informational , 2:major, 3:critical 
MIB TRAP 
Trap # 
niveau 
-upsmgBatteryFault (Nota1) 
Trap 1 
Level 3 
-upsmgBatteryOK (Nota1) 
Trap 2 
Level 1 
-upsmgAtLowBattery (Nota1) 
Trap 5 
Level 3 
-upsmgFromLowBattery (Nota1) 
Trap 6 
Level 1 
-upsmgChargerFault (Nota1) 
Trap 7 
Level 3 
-upsmgChargerOK (Nota1) 
Trap 8 
Level 1 
-upsmgOnBattery (Nota1) 
Trap 11 
Level 2 
-upsmgReturnFromBattery (Nota1) 
Trap 12 
Level 1 
-upsmgOnByPass 
Trap 13 
Level 2 
-upsmgReturnFromByPass 
Trap 14 
Level 1 
-upsmgUtilityFailure 
Trap 17 
Level 2 
-upsmgUtilityRestored 
Trap 18 
Level 1 
-upsmgOverLoad 
Trap 21 
Level 3 
-upsmgLoadOK 
Trap 22 
Level 1 
-upsmgOverTemperature (Nota1) 
Trap 23 
Level 3 
-upsmgTemperatureOK (Nota1) 
Trap 24 
Level 1 
-upsmgOffInProgress (Nota1) 
Trap 31 
Level 3
 
-upsmgCommunicationFailure 
Trap 37 
Level 3 
-upsmgCommunicationRestored 
Trap 38 
Level 1 
-upsmgRedundancyLost 
Trap 65 
Level 2 
-upsmgRedundancyOK 
Trap 66 
Level 2 
-upsmgProtectionLost 
Trap 67 
Level 2 
-upsmgProtectionOK 
Trap 68 
Level 2 
Nota1: This Information is not present with a Static Switch Cabinet unit. 
 
If the Environment Sensor is detected , the following information are managed.: 
- upsEnvironmentComFailure 
Trap 53 
Level 2 
- upsEnvironmentComOK 
Trap 54 
Level 2 
- upsEnvironmentTemperatureLow 
Trap 55 
Level 2 
- upsEnvironmentTemperatureHigh 
Trap 56 
Level 2 
- upsEnvironmentTemperatureOK 
Trap 57 
Level 2 
- upsEnvironmentHumidityLow 
Trap 58 
Level 2 
- upsEnvironmentHumidityHigh 
Trap 59 
Level 2 
- upsEnvironmentHumidityOK 
Trap 60 
Level 2 
- upsEnvironmentInput1Closed 
Trap 61 
Level 2 
- upsEnvironmentInput1Open 
Trap 62 
Level 2 
- upsEnvironmentInput2Open 
Trap 64 
Level 2 
- upsEnvironmentInput2Closed 
Trap 63 
Level 2 
 
The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified applications” page