Site Wiring Requirements, 
Continued 
 
Use approved flexible non-metallic conduit wiring method. Conduit may 
contain multiple cables. For CE installations use only cable gland wiring 
method. 
Non-Hazardous Areas or 
Rack Mounting 
Cable Type: Recommend Belden 9182 or equivalent. Other cables with 
individually shielded pairs can be used, but decreased distance is 
allowed (typically ~800-1000 feet for typical instrumentation cable). 
 
DataNET Fiber Optic 
Cable Connections 
The DataNET channel connections can be either copper wire or fiber 
optic cable. The wiring method and cable type for DataNET is dependent 
upon the site requirements. The following pertains when using copper 
wire. 
See Page 11, CE Installations. 
CE Installations 
Use approved Conduit wiring method. Conduit may contain multiple 
cables. Adhere to all Federal and local electrical code requirements.  
NEC Div 2 or Non-
Hazardous Areas  
Cable Type: Duplex fiber, 62.5/125 micron; see Table 2-1. 
Connection: Type ST fiber connectors. Connect these to the appropriate 
transmitter and receiver ports for the respective channel.  
Use Cable Gland wiring method. Each cable gland allows entry of one 
duplex fiber cable. 
Cenelec Zone 1 or Zone 2 
Rated Areas 
Cable Type: Duplex fiber, 62.5/125 micron. 
Connections: Type ST fiber connectors. Connect these to the 
appropriate transmitter and receiver ports for the respective channel.  
Use approved flexible non-metallic conduit. Conduit may contain multiple 
cables. Conduit may contain multiple. This method is suitable for CE 
installations. 
Non-Hazardous Areas or 
Rack Mounting 
Cable Type: Duplex fiber, 62.5/125 micron. 
Connection: Type ST fiber connectors. Connect these to the appropriate 
transmitter and receiver ports for the respective channel. 
 
10  
  Installation 
2000592-001