Schneider Electric 66123 User Manual

Page of 98
 
 
Network Management Card & Modbus/Jbus                                                                                        34022321XT indice :AE            Page 10/98 
Network Management Teleservice Card 
                 
APC by Schneider Electric  
www.apc.com 
2.4  Administration 
Up to 35 workstations protected by Network Shutdown Modules - Central or local configuration. 
Up to 5 browsers connected at the same time (3 in SSL).  
 
Minimum recommended browser versions: Internet Explorer 6.x / 7.0, Mozilla Firefox 1.5 / 2.0 / 3.0 
E-mail sending configurable according to UPS alarms and transmission of a periodical report. 
Protection by encrypted password.  
Protection by secure SSL connection. 
Saving of logs in the non-volatile memory. 
Languages available:  
 
INMC 66123 : English / French / Spanish / German / Italian 
 
NMTC 66124 : English 
On-line help in English available for each page. 
Card firmware updated via the network 
 
2.5  Network 
Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet. 
 
The used ports are: 
BootP 
 
 
 DHCP 
 
UDP 68 , 67 
HTML 
 
 
TCP 80 
SSL   
 
 
TCP 443 
NSM in connected mode   
TCP 5000 
SMTP  
 
 
25 
SNMP V1 
 
 
161 
TRAP SNMP 
 
 
162 
2.6  Environment sensor 
Temperature measurement from 0 to 70°C with +/- 1°C  accuracy 
Measurement of humidity from 0 to 100% with +/- 6% accuracy 
Min / max time-stamped function for temperature and humidity 
Choice of temperature readings in Celsius or Fahrenheit 
High and low thresholds, hysteresis and offset adjustable via Web interface 
Possibility of notification of status changes by e-mail, SMS or SNMP trap 
Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m) 
Name and status of each configurable contact 
Recording of events and measurements in the card log 
Possibility of shutting down the installation in the event of a threshold being exceeded or on opening / closure of a dry contact 
Connection to the card with straight CAT5 RJ45 network cables (maximum card/sensor distance: 20 m) 
Hot installation 
 
2.7  MIB (Management Information Base) 
Compatible with MIB MGE V1.8 adapted for Galaxy 7000. 
The list of objects managed can be found in the
 
chapter
 
8.2.