Schneider Electric 66123 User Manual

Page of 98
 
 
Network Management Card & Modbus/Jbus                                                                                        34022321XT indice :AE            Page 43/98 
Network Management Teleservice Card 
                 
APC by Schneider Electric  
www.apc.com 
6.4.2  System 
Click on "System" in the menu. 
 
This menu enables the customisation of the information on the UPS properties pages. 
 
UPS Contact: This text field is limited to 49 characters. Enter the name of the person responsible for UPS administration at IT network level 
and/or electrical maintenance. This field does not appear on any other Web page. By default, its value is "Computer Room Manager". 
UPS Location: Enter a description (limited to 49 characters) of the location of the UPS in your installation (e.g. Computer room E1-C066). 
This text is displayed in the home page. By default, its value is "Computer Room". 
Default Language: Enables initialisation of the browser language at card connection.  
Choice of one of the available languages: English, French, German, Spanish, Italian changes the language of the html interface pages (reboot 
the browser after modification). 
History log interval: [from 5 to 99999 sec., 60 by default]. Measurement save period. 
Environment log interval: [from 60 to 99999 sec., 300 by default]. Temperature and humidity measurement save period.  
Reset Communication button: performs a remote reboot of the card without modifying the configuration. This action is compulsory for 
consideration of any changes made on the "Network Settings" page. Security of this operation is ensured by requesting Login and Password. 
Factory Reset button: enables restoration of the default configuration of all the card’s parameters. TCP/IP parameters: IP address, subnet 
mask, gateway and BootP/DHCP value are maintained if the "Keep TCP/IP parameters" option is selected. Security of this operation is 
ensured by requesting Login and Password. The default login and password are: MGEUPS 
Export settings to file: Enables exportation ("Download" button) and saving of card configuration information. 
Import settings from file: Enables selection of a configuration file ("Browse" button) and uploading ("Upload" button) of card configuration 
information.