PANDUIT® DPoE™ Power Patch Panel User’s Guide 
Issue 2.2 
 
 
Part Number: PN378A 
 
 
 
 
 
  
10
 
 
IMPORTANT: 
The  DPOE™ Installation Worksheet should be used to record pertinent 
information when installing DPoE™ Power Patch Panel(s), particularly if the EM is 
monitoring the network.  (See page 29, Provisioning the Panel, for more 
information on how this information will be entered in the EM.)   The installer 
should complete this worksheet.
 
 
Panel Mounting Procedure 
WARNING: 
Only trained and qualified service personnel should install or service 
DPoE™ Power Patch Panels 
 
WARNING: 
Before installing or servicing DPoE™ Power Patch Panels or 
communication wiring, be aware of the hazards with the associated 
electrical circuitry. 
Rack Mounting Instructions 
1.  Record the MAC address, printed on a 
sticker on the back of the unit, by 
writing it in the space provided on the 
included Installation Worksheet 
(PANDUIT part number PN377). 
2.  Slip the Wiring Template Label over 
the rows of connectors on the back of 
the DPoE™ Power Patch Panel, 
making sure the proper wiring code is 
facing out and that the writing is not 
upside down.  One side of the label indicates EIA/TIA 568A wiring, while the other side is EIA/TIA 
568B wiring. 
3.  Using a screw from the US standard thread screw set denoted by “01881-38 REV 2,” attach the 
green and yellow striped grounding strap to the panel via the unthreaded hole nearest the 
power connector
. Next, install the panel onto a grounded rack using the appropriate screw set 
provided to ensure proper grounding between the panel and the rack. Finally, attach the loose 
end of the grounding strap to the rack within the same position as the panel. 
  
PANDUIT Structured Ground Kits for Data Center Rack Grounding can be used to properly ground 
PANDUIT® NetRack Rack Systems and racks from most other manufacturers. 
 
4.  Using four of the enclosed metric or English screws, as appropriate, install the DPoE™ Power 
Panel into the 19” rack at the planned rack position.  
 
WARNING: 
The supplied screws are part of a grounding system to ensure that the 
DPoE™ Power Patch Panel is properly grounded to the rack.   
 
USE ONLY THE SUPPLIED SCREWS TO ATTACH THE PANEL TO 
THE RACK.
 
 
 
Record the rack space position on the Installation Worksheet.