® DPoE™ Power Patch Panel User’s Guide 
Issue 2.2 
 
 
Part Number: PN378A 
 
 
 
 
 
  
35
 
 
panels wired in a single rack will be displayed consistent with the value in the Rack 
Space Position field. (See page 29, Provisioning the Panel, for more information.) 
 
Once these values are set in the EM, this information will be transmitted and stored 
in the DPoE™ Power Patch Panels. 
   
Two additional fields are available on this screen and affect the operation of the 
panel.  The first field, the Power Threshold, allows the network operator to configure 
the available power for this panel as a percentage of the maximum power the panel 
can support. For example, although the panel can support 480 watts, panels that 
use external power supplies, rather than a direct 48-volt input, are not normally 
capable of supplying 480 watts of power. Therefore, the Power Threshold for this 
panel might be set at 30%.  And the Power Warning Threshold, which tells the panel 
when to send an alarm messages, might be set at 10%, so that the panel starts 
alarming when it reaches 90% of this particular panel's maximum. (See page 47, 
EM Log Messages,
 for more information on Power Warning Threshold.)  
 
The Enable Trap is a checkbox (   ) to quickly turn on/off an individual panel’s 
reporting of threshold power alarms. 
 
−  SNMP Settings 
 
The system defaults to public for the SNMP Read Community and private for the 
SNMP Write Community.   
 
IMPORTANT: 
The SNMP Community fields are case-sensitive and allow 
SNMP messages to be exchanged between the EM and the 
DPoE
™ Power Patch Panels.  
  
FOR SECURITY REASONS, THESE FIELDS SHOULD BE 
CHANGED FROM THEIR DEFAULTS. 
 
−  Trap Settings 
 
The Trap Setting section allows the network operator to configure the DPoE™ 
Power Patch Panel to send configuration and alarm messages to up to three 
different IP addresses. 
 
IMPORTANT: 
One of the Traps must be configured and set to the IP address 
of the computer running the EM in order for the EM to receive 
configuration and alarm messages from the panel
 
The computer running the EM should not have any other 
programs running that receive trap information. 
 
 
The IP Address, SNMP Community String and SNMP version (normally SNMP V2C) 
are set according to the destination device for these outgoing messages.  The 
Enable provides an easy on/off button for the traps without having the delete the 
above-entered information. 
 
The other fields, Critical, Major, Minor, Advisory, refer to the priority of the messages 
and allow the network operator to designate which message should be sent to each 
trap.  (See page 47, EM Log Messages, for more information.)