Power supplies
Page 203 of 544
Reserve power
Discharge requirements
Reserve batteries must be able to provide 500 watts of power to each cabinet. 
This is a worst-case figure based on the maximum power consumption per 
cabinet.
Backup options
The options available when backing up the AC-powered Option 11C system 
are as follows:
Use customer-supplied batteries along with the NTAK28 breaker 
assembly. 
Connect an Uninterrupted Power Supply (UPS) to the Option 11C 
system.
Use Nortel Networks supplied NTAK75 or NTAK76 battery units.
Customer supplied reserve batteries with NTAK28
Customer supplied batteries may be used as long they meet the requirements 
set out in Table 64. One NTAK28 breaker assembly is required per cabinet. 
NTAK75 or NTAK76 battery units
Two battery units are available. The NTAK75 supplies a minimum of two 
hours backup at full load, while the NTAK76 supplies a minimum of fifteen 
minutes backup at full load.
CAUTION
Always follow the manufacturer’s instructions when installing 
batteries.
Table 64
Reserve battery requirements
Sealed cells
Cell float voltage
String float voltage
23
2.30 — 2.36
52.95 — 54.25
24
2.20 — 2.26
52.95 — 54.25