Omron CJ1W-EIP21 User Manual

Page of 464
373
Troubleshooting with FINS Response Codes
Section 14-6
10
Command 
format error
01
Command too long
Command 
data
The command is too 
long.
Check the command format of 
the command and set it cor-
rectly.
The command exceeded 
1,473 bytes when broad-
casting.
02
Command too short
Command 
data
The command is too 
short.
03
Number of items 
does not match 
amount of data
Command 
data
The specified number of 
items does not match the 
amount of write data.
Check the number of items 
and amount of data, and 
make them agree.
05
Header parameter 
error
Command 
data
Data for another node on 
the same network was 
received from the net-
work.
Check the command format of 
the command and set it cor-
rectly.
Attempted to send 
response data for a 
broadcast address.
11
Parameter 
error
00
Parameter error
Parameters in 
command 
data
The specified parame-
ters are incorrect.
Check the command data and 
set the parameters correctly.
The UDP/TCP socket 
number was not within 
the proper range.
Be sure the socket number is 
between 1 and 8.
The local UDP port num-
ber might be set to 0.
Set the local UDP port num-
ber correctly.
01
No data area code
Variable type 
in command 
data
A correct memory area 
code has not been used 
or EM Area is not avail-
able.
Check the command’s data 
area code in the Results Stor-
age Area and set the appro-
priate code.
03
Address out-of-
range error
First word 
address in 
command 
data
The first word is in an 
inaccessible area.
Check the data area range, 
and set a first word that is in 
an accessible area.
The specified bit number 
is not 00.
Check the command’s data 
area code in the Results Stor-
age Area. The bit address 
must be 00 for EtherNet/IP 
Units.
04
Address range over-
flow
Command 
data
The address range speci-
fied in the command is 
not correct.
Set the address in the com-
mand data so that the start 
address plus the number of 
words does not exceed 
accessible memory.
0B
Response too long
Command 
data
The response frame is 
longer than allowed.
Correct the number of data 
elements or other parameters 
in the command data for 
which the response is being 
returned.
0C
Parameter error
Parameters in 
command 
data
The specified parame-
ters are incorrect.
Check the command data and 
set the parameters correctly.
21
Cannot 
write
08
Cannot change
IP address 
conversion 
method
A FINS message was 
received from an IP 
address that differed from 
the ones in the Unit 
Setup with FINS node 
addresses that could not 
be dynamically changed.
Correct the relationships 
between IP addresses and 
FINS node addresses. Refer 
to SECTION 5 Determining IP 
Addresses
 fo
r details.
Main response 
code
Sub response code
Item to check
Likely cause
Corrective action
Value and 
meaning
Value and meaning