GE DEH-210 User Manual

Page of 220
PMCS Interface Toolkit
Features of GE Large Faceplate Wizards  
  67
Spectra MicroVersaTrip
®
 Trip Unit
The large faceplate representation of the Spectra MicroVersaTrip
®
 trip unit provides
the following animated functions:
Click on...
Function
Display
Window
Opens the tabular data window specified during wizard
configuration and sets the view to the Normal Monitoring
page.
FUNCTION
Button
Opens the tabular data window specified during wizard
configuration and sets the view to the Setup page.
ENTER Button
Opens the tabular data window specified during wizard
configuration and sets the view to the Setup page.
VALUE Button
Changes phases in appropriate modes, depending on
whether the device has been configured as Wye or Delta
Phase is indicated by letters in the upper right of the
display; press VALUE to display a different phase.
SELECT
Button
Rotates among six different modes, as shown in the lower
left of the display, with units in the lower right.
Table 2. Spectra MVT Faceplate animated functions.
The metering modes available with the SELECT button are as follows:
Mode
Description
AMPS
Current, with no label in the units area of the display. Phase shifting in both
Delta and Wye configurations.
VOLTS
Voltage, displayed as line-to-line (V
L-L
) for Delta and line-to-neutral (VL-N)
for Wye. Phase shifting in both configurations.
ENGY
Energy, displayed in kWh; no phase shifting.
PWR
Real power indicated by non-blinking units symbol (kW). Apparent power
indicated by blinking units symbol. Phase shifting in Wye configuration.
FREQ
Frequency, displayed in Hz. Phase shifting in both Delta and Wye
configurations.