GE EPM9650Q User Manual

Page of 304
73
The EMVT-C’s metering modes available with the SELECT button are as follows:
Mode
Description
AMPS
Current, with no label in the units area of the display. Phase shifting
in both Delta and Wye configurations.
VOLTS
Voltage, displayed as line-to-line (Ph-Ph) for Delta and line-to-
neutral (Ph-N) for Wye. Phases shown as 01, 02, or 03 for Wye and
01 02, 01 03, or 02 03 for Delta.
kWh
Energy; no phase shifting.
kW
Real power; no phase shifting.
kVA
Apparent power; no phase shifting.
Demand
Power demand, displayed with steady kW symbol. Peak power
demand, displayed with blinking kW symbol. No phase shifting.
FREQ
Frequency, displayed in Hz. Phase shifting in both Delta and Wye
configurations.