Liebert Web/485 Leaflet

Page of 2
Liebert Intellislot
®
 Web/485 Card 
With Adapter
Quick Start Guide
I
NSTALL
• Locate the adapter mounting location within your Liebert equipment.
• Secure the card with the supplied screws.
• Connect the equipment's communication cable to the TB1 terminal 
block or P1 on the card (See equipment user manual for details).
• Connect an Ethernet cable to RJ45.
• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal 
block; Pin 1 is at the far left, and Pin 2 is the middle pin.
DHCP: The card ships with DHCP service enabled. The MAC address is 
printed on a sticker affixed to the top of the card.
OR
Static IP: To assign a static IP address, use the Service Terminal to con-
figure the card. Proceed to Steps 2 & 3.
C
ONNECT
 
THE
 C
ABLE
• Locate the blue serial configuration cable (null modem) that shipped 
with the card.
• Connect the configuration cable to the DB-9 port on the card and to a 
COM port on your PC.
C
ONFIGURE
 
THE
 C
ARD
• Use terminal emulation software, such as 
HyperTerminal
, to open a direct connec-
tion to the card.
• Press Enter for the Main Menu.
• Select option 2 and follow the instructions 
to enter an IP ADDRESS,
NETMASK and GATEWAY.
• Press Esc to return to the Main Menu.
• Enter X and press Enter to exit HyperTerminal and save your 
changes.
TB2
(P1: +)
(P2: -);
P1 is at the
right side of 
terminal block.
Network Port 
for NMS and 
Web Access
TB3
(P1: +)
(P2: -)
(P3: NC)
P1 is on 
left end of 
terminal 
block.
DB-9
Port
MAC Address
P1
TB1 (P1: +; P2: -); P1 is at the 
right side of terminal block.
Emulation Software
Configuration
Baud Rate:
9600
Data Bits:
8
Parity:
None
Stop Bits:
1
Flow Control: None