Liebert DS User Manual

Page of 136
Piping Schematics
93
Figure 68 Primary connection locations—downflow water/glycol/GLYCOOL 28-42kW (8-12 ton), all 
compressor models
Point
Description
X
inches (mm)
Y
inches (mm)
Connection Size / Opening
inches (mm)
W
Water/Glycol/GLYCOOL Access
79-15/16 (2030)
9-1/16 (230)
3-1/2 x 8 (89 x 203)
WS
Water/Glycol/GLYCOOL Supply
82-15/16 (2107)
10-15/16 (278)
1-5/8 Cu Sweat
WR
Water/Glycol/GLYCOOL Return
82-15/16 (2107)
14-1/16 (357)
1-5/8 Cu Sweat
CD
Condensate Drain *
46 (1168)
29-1/2 (749)
3/4 FPT
W/ Optional Pump
46 (1168)
29-1/2 (749)
1/2 Cu Sweat
HUM
Humidifier Supply Line
53-1/2 (1359)
29 (737)
1/4 Cu Sweat
ECS 
Econ-O-Coil Supply **
54-7/8 (1394)
22-9/16 (573)
1-5/8 Cu Sweat
ECR 
Econ-O-Coil Return **
49-13/16 (1265)
28-1/2 (724)
1-5/8 Cu Sweat
HS
Hot Water Reheat Supply
Consult Factory
HR
Hot Water Reheat Return
Consult Factory
E1
Electrical Connection (High Volt)
55-1/2 (1410)
31-1/4 (794)
2-1/2
E2
Electrical Connection (High Volt)
52-7/16 (1332)
31-1/4 (794)
2-1/2
LV1
Electrical Connection (Low Volt)
2-1/4 (57)
27 (686)
7/8
LV2
Electrical Connection (Low Volt)
2-1/4 (57)
29 (737)
7/8
LV3
Electrical Connection (Low Volt)
2-1/4 (57)
31 (787)
7/8
B
Blower Outlet
21-15/16 (557)
18-1/16 (459)
18-3/4 x 16-1/16 (476 x 408)
* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do 
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply 
with all local codes.
** Supplied on Dual-Cool systems only (4-pipe system)
8" (203mm)
3-1/2"
(89mm)
Blower 
Outlet
Section A-A
Front View
16-1/16"
(408mm)
B
A
A
X
Y
O
35"
(889mm)
All dimensions 
from rear corner 
of unit including 
panels
Tolerance on all 
piping dimensions 
is ± 1/2" (13mm)
86"
(2184mm)
Front of Unit
Note:  Drawing not to scale
DPN000900
Rev. 2
W
WS
WR
LV3
LV2
LV1
ECS
HUM
CD
ECR
E1 E2