Piping Schematics
97
Figure 72 Primary connection locations—downflow, air-cooled, 105kW (30 ton), all compressor models
Point)
Description)
X
inches (mm)
Y
inches (mm)
Connection Size / Opening
inches (mm)
R
Refrigerant Access
109 (2769)
15-3/4 (400)
16-7/16 x 4 (418 x 102)
L1
Liquid Line System 1
121-3/4 (3092)
16-3/4 (425)
5/8 Cu Sweat
L2
Liquid Line System 2
118-1/8 (3000)
16-3/4 (425)
5/8 Cu Sweat
G1
Hot Gas Discharge 1
118-1/4 (3004)
14-1/4 (362)
1-1/8 Cu Sweat
G2
Hot Gas Discharge 2
115-5/8 (2937)
14-1/4 (362)
1-1/8 Cu Sweat
CD
Condensate Drain *
83-13/16 (2129)
30 (762)
3/4 FPT
W/ Optional Pump
83-13/16 (2129)
30 (762)
1/2 Cu Sweat
HUM
Humidifier Supply Line
102-3/4 (2610)
31-3/4 (806)
1/4 Cu Sweat
ECS** Econ-O-Coil Supply
101-7/8 (2588)
29 (737)
2-5/8 Cu Sweat
ECR** Econ-O-Coil Return
94-9/16 (2402)
29 (737)
2-5/8 Cu Sweat
HS 
Hot Water Reheat Supply
Consult Factory
HR
 Hot Water Reheat Return
Consult Factory
E1
Electrical Connection (High Volt)
98-1/8 (2492)
31-1/4 (794)
2-1/2
E2
Electrical Connection (High Volt)
91 (2311)
31-1/4 (794)
2-1/2
LV1
Electrical Connection (Low Volt)
2 (51)
28-1/4 (718)
7/8
LV2
Electrical Connection (Low Volt)
2 (51)
30-1/4 (768)
7/8
LV3
Electrical Connection (Low Volt)
2 (51)
32 (813)
7/8
B1
Blower Outlet
27-7/8 (708)
18 (457)
14-1/2 x 15-11/16 (368 x 398)
B2
Blower Outlet 
52-1/16 (1322)
18 (457)
14-1/2 x 15-11/16 (368 x 398)
B3
Blower Outlet
 76-1/4 (1937)
18 (457)
14-1/2 x 15-11/16 (368 x 398)
* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not 
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all 
local codes.
** Supplied on Dual-Cool systems only (4-pipe system).
16-7/16"
(418mm)
Section A-A
Front View
A
A
X
Y
O
Tolerance on all 
piping dimensions 
is ± 1/2" (13mm)
131"
(3327mm)
Front of Unit
Note: Drawing not to scale
DPN001014
Rev. 2