Liebert DS User Manual

Page of 136
Liebert DS Dimensions and Weights
21
Figure 16 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all 
compressor models
Table 13
Weights for upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Compressor Type
Dry Weight, lb (kg) approximate
Model
028-042
Semi-Hermetic
Water/Glycol
1980 (898)
GLYCOOL/Dual-Cool 2130 
(966)
Scroll or Digital Scroll
Water/Glycol 1830 
(830)
 GLYCOOL/Dual-Cool 
1980 (898)
DPN001164
Rev. 1
Alternate Refrigerant 
Piping Entrance 
3/4" 
(19mm) Bezels 
24"
(610mm)
34" 
(864mm) 
85" 
(2159mm) 
FRONT VIEW 
Shaded area indicates a 
recommended minimum 
clearance for component 
access. 
2" 
(51mm) 
76" 
(1930mm) 
1-1/2" 
(38mm) 
TOP VIEW 
86" 
(2184mm) 
High Volt Connection(s) 
Condenser Cleanout Access 
35" 
(889mm) 
33" 
(838mm) 
Minimum required 
for blower replacement 
Required for 
condenser cleanout 
Low Volt Connection(s) 
Note: Front air return unit shown. For rear 
return unit, in addition to front service area 
shown, also include 25" (635mm) on one side 
of unit for access to rear return filter box.
See DPN001196, Figure 28